| NATURAL GAS OR PROPANE GENERATING SETS WITH GRAL MOTORS ENGINES |
| |
|
|
|
|
|
|
|
|
|
| GENSET |
60 Hz |
50 Hz |
ENGINE |
|
| MODEL |
1800 rpm 3 phase – 0.8 pf |
1500 rpm 3 phase – 0.8 pf |
MODEL |
| |
|
|
|
|
|
| |
STANDBY |
PRIME |
STANDBY |
PRIME |
|
DIMENSIONS
AND WEIGHT* |
| |
kW (kVA) |
kW (kVA) |
kW (kVA) |
kW (kVA) |
|
L [in] |
W [in] |
H [in] |
Dry Wt [lb] |
| |
|
|
|
|
|
|
|
|
|
| GM30Si |
30 (38) |
27 (34) |
23 (29) |
20 (25) |
VORTEC 3.0L |
78 |
37 |
54 |
1508 |
| |
|
|
|
|
|
|
|
|
|
| GM35Si |
38 (48) |
35 (44) |
31 (39) |
29 (36) |
VORTEC 4.3L |
78 |
37 |
54 |
1728 |
| |
|
|
|
|
|
|
|
|
|
| GM45Si |
40 (50) |
36 (45) |
33 (41) |
30 (38) |
VORTEC 4.3L |
78 |
37 |
54 |
1728 |
| |
|
|
|
|
|
|
|
|
|
| GM60Si |
60 (75) |
55 (69) |
49 (61) |
45 (56) |
VORTEC 5.7L |
90 |
37 |
65 |
2311 |
| |
|
|
|
|
|
|
|
|
|
| GM80Si |
80 (73) |
73 (91) |
66 (83) |
60 (75) |
VORTEC 5.7L |
90 |
37 |
65 |
2439 |
| |
|
|
|
|
|
|
|
|
|
| GM100Si |
90 (113) |
81 (101) |
76 (95) |
69 (86) |
VORTEC 8.1L |
90 |
37 |
65 |
2564 |
| |
|
|
|
|
|
|
|
|
|
| GM125Si |
125 (156) |
115 (144) |
104 (130) |
96 (120) |
VORTEC 8.1LT |
94 |
37 |
65 |
2691 |
|
|
|
|
|
|
|
|
|
|
|
- STANDARD EQUIPMENT:
The engine and the generator are mounted on a steel base on vibration isolators, There is a fuel tank integrated, radiator for tropical conditions, industrial silencer with rain cap. The complete unit is tested to full load plus 10% in a load bank
|
- GENERAL MOTORS (G.M.) ENGINE:
To work with natural gas or liquid propane gas (LPG), water radiator cooled, mechanical governor, industrial air filter, 12 Vcd motor Start and battery charging alternator, Automatic stop protection for failures of high water temperature and low lubricating oil pressure.
|
- ALTERNATOR:
Brushless with one bearing directly coupled to the engine. With automatic voltage regulator.
|
- AUTOMATIC STOP PROTECTION:
For failures of high water temperature and low lubricating oil pressure.
|
- INSTRUMENT PANEL:
Mounted on the unit on vibration isolators model M6 with voltmeter, ammeter, with A/V selector switch, hour counter, frequency and RPM meter, main key start switch.
|
- OPTIONS:
These units are assembled according to the customer’s requirements and therefore they can have all the options required by the customer like: weather or sound attenuation enclosures, automatic transfer switches, or any other type of electrical controls, even computerized.
|
|
|
|
|
|
|
|
|